Ventilation air volume is determined for each premise separately considering concentration of harmful substances. Alternatively, ventilation air volume calculated be set according to the research results. If the nature and concentration of harmful substances is not possible to determine, air exchanged is calculated as following:

L = Vprem. * Ach [m³/h],

where Vprem. – premise volume [m³];

Ach – minimum air exchange per hour, refer air exchange table.

How to determine a premise volume?

Use a simple formula:

length x width x height = volume of the premises in
cubic meters
A x B x H = V [m³]


Example: a premise with 7 m length, 4 m width and 2.8 m height. To determine the air volume required for ventilation of this premises, calculate the room volume 7x4x2.8=78.4 m³. After that determine the required efficiency of the fan using the following tables of recommended ventilation rate.

Calculation of air exchange according to number of inhabitants:

L = L1 * NL (m³/hour),

where L1 – rated value for air volume per one person, m³/h*person;

NL – number of inhabitants in the premises


20-25 m³/h per one person at low physical activity

45 m³/h per one person at light physical activity

60 m³/h per one person at heavy physical activity

Calculation of air exchange with vapor emission:

L= D / ((dv-dn) * ρ) (m³/hour)

where D – moisture, g/hour
dv – moisture content in the exhaust air, gram of water/kg of air
dn – moisture content in the intake air, gram of water/kg of air
ρ – air density, kg/m³ (at 20 °C = 1.205 kg/m³)

Calculation of air exchange to remove excessive heat:

L= Q / (ρ * Cp*(tv-tn)) (m³/hour)

where Q – heat emission in the premises, kW
tv – exhaust air temperature, °С
tn – intake air temperature, °С
ρ – air density, kg/m³ at 20°С = 1.205 kg/m³);
Cp – heat capacity of air [kJ/(kg.K)] at 20°С; Cp=1.005 kJ/(kg.K)

Air ventilation rate:

Domestic premisesAir exchange rate
Living room of apartments or hostel residential premises3 m³/h for 1m² in residential premises
Kitchen in flat or hostel6-8
Bathroom7-9
Shower cabin7-9
WC8-10
Home laundry room7
Cloakroom1,5
Storeroom1
Garage4-8
Cellar

4-6


Industrial premises and large premisesPremise Air exchange rate
Theatre, cinema, confrence hall20-40 m³ per each visitor
Office5-7
Bank2-4
Restaurant8-10
Bar, café, pub, billiard room9-11
Professional kitchen10-15
Supermarket1,5-3
Chemist’s3
Garages and vehicle repair shops6-8
Public WC10-12 (or 100 m³ per each WC pan)
Dance halls and disco clubs8-10
Smoking rooms10
Server rooms5-10
Sport hall80 m³ or more for each sportsman and 20 m³ or more for each viewer
Hair dresser's up to 5 working places2
Hair dresser's more than 5 working places3
Warehouses1-2
Laundryroom10-13
Swimming pool10-20
Industrial painting shop25-40
Machine shop3-5
School classroom3-8


Calculation of air exchange depending on maximum permissible concentration of aggressive substances in the air:

L= GCO2 / (UPDК-UP) (m³/hour)

де GСО2 – СОrelease amount [l/hour]
 UPDК – СО2 maximum permissible concentration, l/m³
 UP – gas concentration in the intake air, l/hour

CO2 permissible concentration norms, l/m³
Permanent residential premises1,0
Hospitals and child care centers0,7
Periodically occupied premises1,25
Short stay premises2,0
Open air:Populations centers (village)0,33
Small towns0,4
Big cities0,5