Vents Boost 200

Inline fans in a polymer casing
  • Maximum airflow: 1140 m3/h
  • Sound pressure level LpA at 3 m: 50 dB(A)
  • Motor type: AC
  • Impeller type: Mixed-flow
  • Casing material: Plastic
  • Installation in any position
Unit of measurement Boost 200
Connected air duct size mm 200
Speed - 1 2 3
Minimum supply voltage V 230
Maximum supply voltage V 230
Power supply frequency Hz 50
Rated power W 82 101 113
Unit current A 0.37 0.45 0.51
Maximum airflow m3/h 752 978 1140
Sound pressure level LpA at 3 m dB(A) 39 46 50
Transported air temperature (max) °С 55
Transported air temperature (min) °С -25
Ingress protection rating - IPX4
Ingress protection rating of the drive - IP20
Trademark Vents
Model Boost 200
Type of drive installed Integrated VSD
Type of heat recovery system None
Nominal flow rate (m3/s) 0.193
Nominal external pressure (Pa) 183
Maximum external leakage rates (%) 2.7
Static efficiency (%) 33.3
Declared typology NRVU UVU
Effective electric power input (kW) 0.108
Sound power level (dB(A)) 70
Datasheet
"VENTS BOOST" product description 08-2023
1.52 Mb
Manual
"VENTS BOOST 315/355/400 (EC)" user's manual 04-2024 (V208EN-06)
1.64 Mb
Manual
"VENTS BOOST 150/160/200/250 (EC)" user's manual 02-2024 (V208-1EN-03)
1.34 Mb
BIM/CAD models
Boost (EC)
2.79 Mb
Image
Boost 200 - image 1
435 Kb
∅D ∅D1 A H
199 293 302 308