Unit of measurement | Boost 250 | |||
Connected air duct size | mm | 250 | ||
Speed | - | 1 | 2 | 3 |
Minimum supply voltage | V | 230 | ||
Maximum supply voltage | V | 230 | ||
Power supply frequency | Hz | 50 | ||
Rated power | W | 144 | 173 | 188 |
Unit current | A | 0.70 | 0.81 | 0.84 |
Maximum airflow | m3/h | 1038 | 1447 | 1715 |
Sound pressure level LpA at 3 m | dB(A) | 41 | 47 | 50 |
Transported air temperature (max) | °С | 55 | ||
Transported air temperature (min) | °С | -25 | ||
Ingress protection rating | - | IPX4 | ||
Ingress protection rating of the drive | - | IP20 |
Trademark | Vents |
Model | Boost 250 |
Type of drive installed | Integrated VSD |
Type of heat recovery system | None |
Nominal flow rate (m3/s) | 0.265 |
Nominal external pressure (Pa) | 248 |
Maximum external leakage rates (%) | 2.7 |
Static efficiency (%) | 39.5 |
Declared typology | NRVU UVU |
Effective electric power input (kW) | 0.17 |
Sound power level (dB(A)) | 62 |