Unit of measurement | DuoVent 250 EC | ||
Connected air duct size | mm | 250 | |
Minimum supply voltage | V | 220 | |
Maximum supply voltage | V | 240 | |
Power supply frequency | Hz | 50/60 | |
Rated power | W | 170 | |
Unit current | A | 1.29 | |
Maximum airflow | m3/h | 1390 | |
Sound pressure level LpA at 3 m | dB(A) | 49 | |
Weight | kg | 47 | |
Transported air temperature (max) | °С | 55 | |
Transported air temperature (min) | °С | -25 | |
Ingress protection rating | - | IPX4 | |
Ingress protection rating of the drive | - | IP54 | IP44 |
Trademark | Vents |
Model | DuoVent 250 EC |
Type of drive installed | External MSD or VSD |
Type of heat recovery system | None |
Nominal flow rate (m3/s) | 0.277 |
Nominal external pressure (Pa) | 188 |
Maximum external leakage rates (%) | 2.7 |
Static efficiency (%) | 47.4 |
Effective electric power input (kW) | 0.17 |
Sound power level (dB(A)) | 64 |
Declared typology | NRVU UVU |
D | L | L1 | H | W | W1 |
---|---|---|---|---|---|
249 | 1062 | 939 | 417 | 887 | 806 |