Vents DVUT 300 PBE EC A21 V.2

Suspension-mounted single-room air handling units in a heat- and sound insulated casing
  • Power of electrical preheater: 1050 W
  • Maximum airflow: 300 m3/h
  • Sound pressure level LpA at 3 m: 34 dB(A)
  • Sound pressure level LpA at 1 m: 44 dB(A)
  • Heat exchanger type: Counter flow
  • Extract filter: ISO Coarse >60% (G4)
  • Supply filter: ISO ePM1 60% (F7)
  • Sound insulation
  • Motor type: EC
  • Bypass: Auto
  • Reheater: Electric
  • BMS protocol: ModBus
  • Control: Smartphone
  • Casing material: Galvanized steel
  • Humidity sensor: Optional
  • CO2 sensor: Optional
  • VOC sensor: Optional
  • Temperature sensor: Built-in
Unit of measurement DVUT 300 PBE EC A21 V.2
Connected air duct size mm 200
Minimum supply voltage V 230
Maximum supply voltage V 230
Power supply frequency Hz 50/60
Rated power W 97
Power of electrical preheater W 1050
Unit current A 0.8
Maximum airflow m3/h 300
Sound pressure level LpA at 3 m dB(A) 34
Sound pressure level LpA at 1 m dB(A) 44
Heat recovery efficiency, max % 92
Heat exchanger type - Counter flow
Heat exchanger material - Polystyrene
Weight kg 79
Extract filter - ISO Coarse >60% (G4)
Supply filter - ISO ePM1 60% (F7)
Transported air temperature (max) °С 40
Transported air temperature (min) °С -25
Ambient air temperature min °С 1
Ambient air temperature max °С 40
Ambient air humidity max % 60
Ingress protection rating - IP20
Ingress protection rating of the drive - IP44
Datasheet
"Single-room ventilation for schools and public spaces" catalog 2024
4.91 Mb
Manual
"DVUT PB EC V.2" user's manual 04-2024 (V177EN-06)
4.45 Mb
Manual
"DVUT 1000 PB EC V.2" user's manual 03-2023 (V177-1EN-03)
6.27 Mb
Manual
"DVUT 1000 PB EC V.2" user's manual 04-2024 (V177-1EN-03)
6.27 Mb
Manual
"BMS parameter table for PCOS004850 module for DVUT units" user’s manual 07-2020 (V197-1EN-02)
73 Kb
Manual
"Wireless control system A21" user’s manual 02-2023 (V55-8EN-05)
504 Kb
Image
DVUT 300 PBE EC A21 V.2 - image 1
216 Kb
Vents DVUT 300 PBE EC A21 V.2 - Dimensions
∅D A A1 A2 A3 B B1 B2 B3 H H1 N M
200 1200 867 166 1122 850 181 530 207 402 202 445 41
Name Photo Description
Vents MVMA 200 bVn Al MVMA 200 bVn Al Supply and exhaust metal grille
Name Photo Description
Vents DPWQ30600 DPWQ30600 VOC sensors
Vents DPWQ40200 DPWQ40200 CO2 sensor
Name Photo Description
Vents DPWC11200 DPWC11200 Humidity sensor
Vents HR-S HR-S Electro-mechanical humidistats
Vents HV2 HV2 Humidity sensor
Vents CO2-1 CO2-1 CO2 sensors
Vents CO2-2 CO2-2 CO2 sensors
Vents CO2-3 CO2-3 CO2 sensor
Name Photo Description
Vents DN-2 DN-2 The drain pump provides extraction and discharge of condensate in ventilation systems
Vents SH-32 SH-32 The hydraulic U-trap for condensate drainage from heat exchangers and coolers in ventilation and air conditioning systems
Vents DN-2-DVUT P DN-2-DVUT P Drain pump kit box