Vents KSB 100

Inline centrifugal fans in heat- and sound-insulated casing
  • Maximum airflow: 240 m3/h
  • Sound pressure level LpA at 3 m: 33 dB(A)
  • Sound insulation
  • Motor type: AC
  • Impeller type: Centrifugal backward curved blades
  • Casing material: Galvanized steel
  • Installation in any position
Unit of measurement KSB 100
Connected air duct size mm 100
Minimum supply voltage V 220
Maximum supply voltage V 240
Power supply frequency Hz 50/60
Rated power W 73
Unit current A 0.32
Maximum airflow m3/h 240
Sound pressure level LpA at 3 m dB(A) 33
Weight kg 5.4
Transported air temperature (max) °С 55
Transported air temperature (min) °С -25
Ingress protection rating - IPX4
Vents KSB 100 33 205 2016
Trademark Vents
Model KSB 100
Specific energy consumption (SEC) (kWh/(m2/a)) Cold Average Warm
-50.1 A+ -23.1 C -7.6 F
Type of ventilation unit Unidirectional
Type of drive installed Multi-speed
Type of heat recovery system None
Maximum flow rate (m3/h) 205
Electric power input (W) 73
Reference flow rate (m3/s) 0.04
Reference pressure difference (Pa) 50
Specific power input (SPI) (W/(m3/h)) 0.28
Control typology Local demand control
Maximum external leakage rates (%) 2.7
Declared typology RVU UVU
Sound power level (dB(A)) 33
The annual electricity consumption (AEC) (kWh/a) Cold Average Warm
209 209 209
The annual heating saved (AHS) (kWh/a) Cold Average Warm
5536 2830 1280
Datasheet
"VENTS KSB" product description 05-2023
2.28 Mb
Manual
"VENTS KSB" user's manual 08-2024 (V51EN-06)
2.64 Mb
Image
KSB 100 - image 1
504 Kb
∅D B B1 H L L1 L2
99 322 280 192 447 380 350