| Unit of measurement | MPA 400 E-2.4 EC A31 | |
| Connected air duct size | mm | 200 |
| Minimum supply voltage | V | 230 |
| Maximum supply voltage | V | 230 |
| Power supply frequency | Hz | 50 |
| Rated power | W | 62 |
| Power of electrical reheater | W | 2400 |
| Unit current | A | 12 |
| Maximum airflow | m3/h | 430 |
| Sound pressure level LpA at 3 m | dB(A) | 31 |
| Weight | kg | 25 |
| Filter | - | Coarse 90% / G4 (option ePM1 70% / F7) |
| Transported air temperature (max) | °С | 40 |
| Transported air temperature (min) | °С | -30 |
| Ingress protection rating | - | IP22 |
| Ingress protection rating of the drive | - | IP44 |
| Trademark | Vents | |||||
| Model | MPA 400 E-2.4 EC A31 | |||||
| Specific energy consumption (SEC) (kWh/(m2/a)) | Cold | Average | Warm | |||
| -54 | A+ | -26.9 | B | -11.4 | E | |
| Type of ventilation unit | Unidirectional | |||||
| Type of drive installed | Variable speed | |||||
| Type of heat recovery system | None | |||||
| Maximum flow rate (m3/h) | 310 | |||||
| Electric power input (W) | 62 | |||||
| Reference flow rate (m3/s) | 0.061 | |||||
| Reference pressure difference (Pa) | 50 | |||||
| Specific power input (SPI) (W/(m3/h)) | 0.105 | |||||
| Control typology | Local demand control | |||||
| Maximum internal leakage rates (%) | 2.7 | |||||
| Maximum external leakage rates (%) | 2.7 | |||||
| Sound power level (dB(A)) | 36 | |||||
| Declared typology | RVU UVU | |||||
| The annual electricity consumption (AEC) (kWh/a) | Cold | Average | Warm | |||
| 55 | 55 | 55 | ||||
| The annual heating saved (AHS) (kWh/a) | Cold | Average | Warm | |||
| 5536 | 2830 | 1280 | ||||
| Name | Photo | Description |
|---|---|---|
| Vents SR 200/600 |
|
Silencers made of galvanized steel filled with non-combustible sound-absorbing material |
| Vents SR 200/900 |
|
Silencers made of galvanized steel filled with non-combustible sound-absorbing material |
| Vents SR 200/1200 |
|
Silencers made of galvanized steel filled with non-combustible sound-absorbing material |
| Name | Photo | Description |
|---|---|---|
| Vents KRV 200 |
|
Air dampers for automatic air flow control in round ducts |
| Name | Photo | Description |
|---|---|---|
| Vents VVG 200 |
|
Flexible anti-vibration inserts for round ducts |
| Name | Photo | Description |
|---|---|---|
| Vents Belimo TF24 |
|
The actuators are designed for controlling air dampers with cross section up to 0.4 m² performing protection functions |
| Vents Belimo TF230 |
|
The actuators are designed for controlling air dampers with cross section up to 0.4 m² performing protection functions |
| Name | Photo | Description |
|---|---|---|
| Vents SF 334x287x48 G4 |
|
Panel filter G4 |
| Vents SF 334x287x48 F7 |
|
F7 panel filter |