Vents OV 4E 500

Wall-mounted axial fans
  • Sound pressure level LpA at 3 m: 58 dB(A)
  • Impeller type: Axial
  • Casing material: Coated steel
  • Installation in any position
Unit of measurement OV 4E 500
Connected air duct size mm 500
Phases - 1
Maximum supply voltage V 240
Minimum supply voltage V 220
Power supply frequency Hz 50
Rated power W 420
Unit current A 1.95
Maximum airflow m³/h 7060
Rotation speed at 50hz - 1300
Sound pressure level LpA at 3 m dB(A) 58
Weight kg 14
Transported air temperature (max) °С 60
Transported air temperature (min) °С -30
Ingress protection rating - IP24
Ingress protection rating of the drive - IP54
Impeller material - Coated steel
Trademark Vents
Model OV 4E 500
Type of drive installed External MSD or VSD
Type of heat recovery system None
Nominal external pressure (Pa) 100
Maximum external leakage rates (%) 2.7
Static efficiency (%) 32.1
Sound power level (dB(A)) 89
Effective electric power input (kW) 0.44
Declared typology NRVU UVU
Datasheet
"VENTS OV, OVK, VKF" product description 12-2025
2.18 Mb
Manual
"VENTS OV,OVK,OV1,OV1 R,OVK1,VKF,VKOM,OVP,VKOM(z),VKOM1(z)" user's manual 08-2025 (V03EN-13)
5.57 Mb
Certificates
Certificate GS "OV, OVK 200-450 (2E, 4E)"
1.76 Mb
Image
OV 4E 500 - image 1
577 Kb
∅D ∅d B B1 L
520 11 655 615 250