Vents TT PRO 200

Inline mixed-flow fans
  • Maximum airflow: 1040 m3/h
  • Sound pressure level LpA at 3 m: 45 dB(A)
  • Motor type: AC
  • Impeller type: Mixed-flow
  • Casing material: Plastic
  • Installation in any position
Unit of measurement TT PRO 200
Connected air duct size mm 200
Speed - 1 2
Minimum supply voltage V 230
Maximum supply voltage V 230
Power supply frequency Hz 50/60
Rated power W 76 108
Unit current A 0.34 0.48
Maximum airflow m3/h 830 1040
Sound pressure level LpA at 3 m dB(A) 39 45
Weight kg 3.95
Transported air temperature (max) °С 60
Ingress protection rating - IPX4
Ingress protection rating of the drive - IPX4
Vents TT PRO 200 72 800 2016
Trademark Vents
Model TT PRO 200
Specific energy consumption (SEC) (kWh/(m2/a)) Cold Average Warm
-53.6 A+ -26.5 B -11 E
Type of ventilation unit Unidirectional
Type of drive installed Variable speed
Type of heat recovery system None
Maximum flow rate (m3/h) 800
Electric power input (W) 108
Reference flow rate (m3/s) 0.156
Reference pressure difference (Pa) 50
Specific power input (SPI) (W/(m3/h)) 0.136
Control typology Local demand control
Maximum external leakage rates (%) 2.7
Declared typology RVU UVU
Sound power level (dB(A)) 72
The annual electricity consumption (AEC) (kWh/a) Cold Average Warm
72 72 72
The annual heating saved (AHS) (kWh/a) Cold Average Warm
5536 2830 1280
Datasheet
"VENTS TT PRO" product description 05-2022
2.01 Mb
Manual
"VENTS TT PRO" user's manual 09-2023 (V77EN-05)
1.55 Mb
Image
TT PRO 200 - image 1
480 Kb
Vents TT PRO 200 - Dimensions
∅D B H L
199 239 261 295.5