Unit of measurement | VKM 400 | |
Connected air duct size | mm | 400 |
Minimum supply voltage | V | 220 |
Maximum supply voltage | V | 240 |
Power supply frequency | Hz | 50/60 |
Rated power | W | 460 |
Unit current | A | 2.23 |
Maximum airflow | m3/h | 3090 |
Sound pressure level LpA at 3 m | dB(A) | 61 |
Weight | kg | 25.1 |
Transported air temperature (max) | °С | 80 |
Transported air temperature (min) | °С | -40 |
Ingress protection rating | - | IPX4 |
Ingress protection rating of the drive | - | IP54 |
Trademark | Vents |
Model | VKM 400 |
Type of drive installed | External MSD or VSD |
Type of heat recovery system | None |
Nominal flow rate (m3/s) | 0.419 |
Nominal external pressure (Pa) | 312 |
Maximum external leakage rates (%) | 2.7 |
Static efficiency (%) | 29.7 |
Declared typology | NRVU UVU |
Sound power level (dB(A)) | 81 |
Effective electric power input (kW) | 0.449 |
ØD | ØD1 | B | B1 | L | L1 | L2 | L3 |
---|---|---|---|---|---|---|---|
398 | 570 | 663 | 634 | 570 | 60 | 60 | 70 |