Unit of measurement | VKM 450 | |
Connected air duct size | mm | 450 |
Minimum supply voltage | V | 220 |
Maximum supply voltage | V | 240 |
Power supply frequency | Hz | 50/60 |
Rated power | W | 665 |
Unit current | A | 2.89 |
Maximum airflow | m3/h | 5300 |
Sound pressure level LpA at 3 m | dB(A) | 65 |
Weight | kg | 27.26 |
Transported air temperature (max) | °С | 70 |
Transported air temperature (min) | °С | -40 |
Ingress protection rating | - | IPX4 |
Ingress protection rating of the drive | - | IP54 |
Trademark | Vents |
Model | VKM 450 |
Type of drive installed | External MSD or VSD |
Type of heat recovery system | None |
Nominal flow rate (m3/s) | 0.717 |
Nominal external pressure (Pa) | 350 |
Maximum external leakage rates (%) | 2.7 |
Static efficiency (%) | 42.9 |
Declared typology | NRVU UVU |
Effective electric power input (kW) | 0.596 |
Sound power level (dB(A)) | 85 |