| Unit of measurement | VKP 400x200 L1 EC | |
| Connected air duct size | mm | 400x200 |
| Minimum supply voltage | V | 230 |
| Maximum supply voltage | V | 230 |
| Power supply frequency | Hz | 50/60 |
| Rated power | W | 192 |
| Unit current | A | 1.43 |
| Maximum airflow | m3/h | 1190 |
| Sound pressure level LpA at 3 m | dB(A) | 47 |
| Weight | kg | 10 |
| Transported air temperature (max) | °С | 50 |
| Transported air temperature (min) | °С | -25 |
| Ingress protection rating | - | IPX4 |
| Ingress protection rating of the drive | - | IP54 |
| Impeller material | - | Plastic |
| Trademark | Vents |
| Model | VKP 400x200 L1 EC |
| Type of drive installed | Integrated VSD |
| Type of heat recovery system | None |
| Nominal flow rate (m3/s) | 0.161 |
| Nominal external pressure (Pa) | 504 |
| Maximum external leakage rates (%) | 2.7 |
| Static efficiency (%) | 54.2 |
| Effective electric power input (kW) | 0.174 |
| Declared typology | NRVU UVU |
| Sound power level (dB(A)) | 67 |