Vents VKP 4E 600x300

Centrifugal fans for rectangular ducts
  • Maximum airflow: 2470 m3/h
  • Sound pressure level LpA at 3 m: 52 dB(A)
  • Motor type: AC
  • Impeller type: Centrifugal backward curved blades
  • Casing material: Galvanized steel
  • Installation in any position
Unit of measurement VKP 4E 600x300
Connected air duct size mm 600x300
Minimum supply voltage V 220
Maximum supply voltage V 240
Power supply frequency Hz 50/60
Rated power W 220
Unit current A 0.9
Maximum airflow m3/h 2470
Sound pressure level LpA at 3 m dB(A) 52
Weight kg 27.77
Transported air temperature (max) °С 45
Transported air temperature (min) °С -25
Ingress protection rating - IPX4
Ingress protection rating of the drive - IP44
Trademark Vents
Model VKP 4E 600x300
Type of drive installed External MSD or VSD
Type of heat recovery system None
Nominal flow rate (m3/s) 0.271
Nominal external pressure (Pa) 300
Maximum external leakage rates (%) 2.7
Static efficiency (%) 39.6
Declared typology NRVU UVU
Sound power level (dB(A)) 75
Effective electric power input (kW) 0.21
Datasheet
"VENTS VKP (for rectangular ducts), VKPI" product description 09-2023
2.38 Mb
Manual
"VENTS VKP, VKPI, VKPF, VKPFI, VKP EC, VKPI EC" user's manual 08-2022 (V07EN-05)
3.78 Mb
BIM/CAD models
VKP (rectangular)
2.39 Mb
BIM/CAD models
VKP 1000х500 (rectangular)
1.44 Mb
Image
VKP 4E 600x300 - image 1
558 Kb
B B1 B2 H H1 H2 H3 L
600 620 640 300 320 340 342 680