Vents VKP 500x250 M1 EC

Centrifugal fans for rectangular ducts
  • Maximum airflow: 1590 m3/h
  • Sound pressure level LpA at 3 m: 45 dB(A)
  • Motor type: EC
  • Impeller type: Centrifugal backward curved blades
  • Casing material: Galvanized steel
  • Installation in any position
Unit of measurement VKP 500x250 M1 EC
Connected air duct size mm 500x250
Minimum supply voltage V 230
Maximum supply voltage V 230
Power supply frequency Hz 50/60
Rated power W 252
Unit current A 1.85
Maximum airflow m3/h 1590
Sound pressure level LpA at 3 m dB(A) 45
Weight kg 15.7
Transported air temperature (max) °С 50
Transported air temperature (min) °С -25
Ingress protection rating - IPX4
Ingress protection rating of the drive - IP54
Trademark Vents
Model VKP 500x250 M1 EC
Type of drive installed Integrated VSD
Type of heat recovery system None
Nominal flow rate (m3/s) 0.213
Nominal external pressure (Pa) 330
Maximum external leakage rates (%) 2.7
Static efficiency (%) 53.1
Declared typology NRVU UVU
Effective electric power input (kW) 0.154
Sound power level (dB(A)) 65
Datasheet
"VENTS VKP EC" product description 09-2023
4.38 Mb
Manual
"VENTS VKP, VKPI, VKPF, VKPFI, VKP EC, VKPI EC" user's manual 08-2022 (V07EN-05)
3.78 Mb
Manual
"VENTS VKP EC" user's manual 11-2022 (V197EN-02)
1.99 Mb
Image
VKP 500x250 M1 EC - image 1
559 Kb
B B1 B2 H H1 H2 H3 L
500 520 540 250 270 290 328 530