Unit of measurement | VKP 800x500 L3 EC | |
Connected air duct size | mm | 800x500 |
Minimum supply voltage | V | 400 |
Maximum supply voltage | V | 400 |
Power supply frequency | Hz | 50/60 |
Rated power | W | 2925 |
Unit current | A | 3.05 |
Maximum airflow | m3/h | 8535 |
Sound pressure level LpA at 3 m | dB(A) | 63 |
Weight | kg | 54.3 |
Transported air temperature (max) | °С | 50 |
Transported air temperature (min) | °С | -25 |
Ingress protection rating | - | IPX4 |
Ingress protection rating of the drive | - | IP54 |
Trademark | Vents |
Model | VKP 800x500 L3 EC |
Type of drive installed | Integrated VSD |
Type of heat recovery system | None |
Nominal flow rate (m3/s) | 0.904 |
Nominal external pressure (Pa) | 475 |
Maximum external leakage rates (%) | 2.7 |
Static efficiency (%) | 60.8 |
Declared typology | NRVU UVU |
Effective electric power input (kW) | 0.789 |
Sound power level (dB(A)) | 83 |