| Unit of measurement | VKPF 4D 600x300 | |
| Connected air duct size | mm | 600x300 |
| Minimum supply voltage | V | 400 |
| Maximum supply voltage | V | 400 |
| Power supply frequency | Hz | 50 |
| Rated power | W | 1560 |
| Unit current | A | 2.73 |
| Maximum airflow | m3/h | 3740 |
| Rotation speed at 50hz | - | 1310 |
| Sound pressure level LpA at 3 m | dB(A) | 57 |
| Weight | kg | 35 |
| Transported air temperature (max) | °С | 65 |
| Transported air temperature (min) | °С | -25 |
| Ingress protection rating | - | IPX4 |
| Ingress protection rating of the drive | - | IP44 |
| Trademark | Vents |
| Model | VKPF 4D 600x300 |
| Type of drive installed | External MSD or VSD |
| Type of heat recovery system | None |
| Nominal flow rate (m3/s) | 0.419 |
| Nominal external pressure (Pa) | 485 |
| Maximum external leakage rates (%) | 2.7 |
| Static efficiency (%) | 40.6 |
| Sound power level (dB(A)) | 77 |
| Declared typology | NRVU UVU |
| Effective electric power input (kW) | 0.51 |
| Name | Photo | Description |
|---|---|---|
| Vents SR 600x300 |
|
Plate silencer for installation in rectangular ducts |
| Name | Photo | Description |
|---|---|---|
| Vents FB 600x300 |
|
Rectangular panel air filters |
| Vents FBK 600x300-4 |
|
Rectangular bag air filters |
| Vents FBK 600x300-5 |
|
Rectangular bag air filters |
| Vents FBK 600x300-7 |
|
Rectangular bag air filters |
| Name | Photo | Description |
|---|---|---|
| Vents KG 600x300 |
|
Gravity valve for automatic airflow shut-off in round air ducts |
| Name | Photo | Description |
|---|---|---|
| Vents VVG 600x300 |
|
Flexible anti-vibration inserts for round air ducts |
| Name | Photo | Description |
|---|---|---|
| Vents PR 600x300 |
|
Cross-flow plate heat exchangers for rectangular air ducts |
| Name | Photo | Description |
|---|---|---|
| Vents SKRA 600x300/24 |
|
Mixing chambers for mixing (recirculating) part of the exhaust air with the outdoor air in the appropriate proportion |
| Name | Photo | Description |
|---|---|---|
| Vents NKV 600x300-2 |
|
Inline water supply air heaters or heater for air handling units with a rectangular cross-section |
| Vents NKV 600x300-4 |
|
Inline water supply air heaters or heater for air handling units with a rectangular cross-section |
| Name | Photo | Description |
|---|---|---|
| Vents NK 600x300-9,0-3 |
|
Rectangular electric inline heaters |
| Vents NK 600x300-12,0-3 |
|
Rectangular electric inline heaters |
| Vents NK 600x300-15,0-3 |
|
Rectangular electric inline heaters |
| Vents NK 600x300-18,0-3 |
|
Rectangular electric inline heaters |
| Vents NK 600x300-21,0-3 |
|
Rectangular electric inline heaters |
| Vents NK 600x300-24,0-3 |
|
Rectangular electric inline heaters |
| Vents NK 600x300-9,0-3 U |
|
Rectangular electric inline heaters with control unit |
| Vents NK 600x300-12,0-3 U |
|
Rectangular electric inline heaters with control unit |
| Vents NK 600x300-15,0-3 U |
|
Rectangular electric inline heaters with control unit |
| Vents NK 600x300-18,0-3 U |
|
Rectangular electric inline heaters with control unit |
| Vents NK 600x300-21,0-3 U |
|
Rectangular electric inline heaters with control unit |
| Vents NK 600x300-24,0-3 U |
|
Rectangular electric inline heaters with control unit |
| Name | Photo | Description |
|---|---|---|
| Vents RRV 600x300 |
|
Air flow controllers |
| Name | Photo | Description |
|---|---|---|
| Vents RSA5D-4,0-M |
|
Three phase speed controller |