Vents VKPF 6D 900x500

Inline centrifugal fans for rectangular ducts
  • Maximum airflow: 9540 m3/h
  • Sound pressure level LpA at 3 m: 61 dB(A)
  • Motor type: AC
  • Impeller type: Centrifugal forward curved blades
  • Casing material: Galvanized steel
  • Installation in any position
Unit of measurement VKPF 6D 900x500
Connected air duct size mm 900x500
Minimum supply voltage V 400
Maximum supply voltage V 400
Power supply frequency Hz 50
Rated power W 3870
Unit current A 7
Maximum airflow m3/h 9540
Sound pressure level LpA at 3 m dB(A) 61
Weight kg 90
Transported air temperature (max) °С 55
Transported air temperature (min) °С -20
Ingress protection rating - IPX4
Ingress protection rating of the drive - IP44
Trademark Vents
Model VKPF 6D 900x500
Type of drive installed External MSD or VSD
Type of heat recovery system None
Nominal flow rate (m3/s) 1.441
Nominal external pressure (Pa) 590
Maximum external leakage rates (%) 2.7
Static efficiency (%) 43.2
Declared typology NRVU UVU
Effective electric power input (kW) 2.01
Sound power level (dB(A)) 81
Datasheet
"VENTS VKPF, VKPFI" product description 05-2023
2.71 Mb
Manual
"VENTS VKP, VKPI, VKPF, VKPFI, VKP EC, VKPI EC" user's manual 08-2022 (V07EN-05)
3.78 Mb
BIM/CAD models
VKPF
2.45 Mb
Image
VKPF 6D 900x500 - image 1
537 Kb
B B1 B2 H H1 H2 H3 L
900 920 940 500 520 540 580 954