Vents VKPI 2E 500x250

Centrifugal sound- and heat-insulated fans for rectangular ducts
  • Maximum airflow: 1720 m3/h
  • Sound pressure level LpA at 3 m: 51 dB(A)
  • Sound insulation
  • Motor type: AC
  • Impeller type: Centrifugal backward curved blades
  • Casing material: Galvanized steel
  • Installation in any position
Unit of measurement VKPI 2E 500x250
Connected air duct size mm 500x250
Minimum supply voltage V 220
Maximum supply voltage V 240
Power supply frequency Hz 50/60
Rated power W 305
Unit current A 1.32
Maximum airflow m3/h 1720
Sound pressure level LpA at 3 m dB(A) 51
Weight kg 27.6
Transported air temperature (max) °С 45
Transported air temperature (min) °С -25
Ingress protection rating - IPX4
Ingress protection rating of the drive - IP44
Trademark Vents
Model VKPI 2E 500x250
Type of drive installed External MSD or VSD
Type of heat recovery system None
Nominal flow rate (m3/s) 0.277
Nominal external pressure (Pa) 400
Maximum external leakage rates (%) 2.7
Static efficiency (%) 40.5
Declared typology NRVU UVU
Sound power level (dB(A)) 73
Effective electric power input (kW) 0.279
Datasheet
"VENTS VKP (for rectangular ducts), VKPI" product description 09-2023
2.38 Mb
Manual
"VENTS VKP, VKPI, VKPF, VKPFI, VKP EC, VKPI EC" user's manual 08-2022 (V07EN-05)
3.78 Mb
BIM/CAD models
VKPI
1.7 Mb
Image
VKPI 2E 500x250 - image 1
479 Kb
B B1 B2 B3 H H1 H2 H3 L
500 520 540 600 250 270 290 410 640