Vents VKV 280 EC

Roof exhaust centrifugal fans with vertical air exhaust
  • Maximum airflow: 2330 m3/h
  • Sound pressure level LpA at 3 m: 48 dB(A)
  • Motor type: EC
  • Impeller type: Centrifugal backward curved blades
  • Casing material: Polypropylene/Thermoplastic elastomer
Unit of measurement VKV 280 EC
Minimum supply voltage V 230
Maximum supply voltage V 230
Power supply frequency Hz 50/60
Rated power W 182
Unit current A 1.34
Maximum airflow m3/h 2330
Sound pressure level LpA at 3 m dB(A) 48
Weight kg 13
Transported air temperature (max) °С 60
Transported air temperature (min) °С -20
Ingress protection rating - IPX4
Ingress protection rating of the drive - IP44
Trademark Vents
Model VKV 280 EC
Type of drive installed Integrated VSD
Type of heat recovery system None
Nominal flow rate (m3/s) 0.461
Nominal external pressure (Pa) 423
Maximum external leakage rates (%) 2.7
Static efficiency (%) 52.2
Declared typology NRVU UVU
Effective electric power input (kW) 0.425
Sound power level (dB(A)) 67
Datasheet
"VENTS VKV/ VKH EC" product description 05-2023
2.2 Mb
Manual
"VENTS VKV EC, VKH EC" user's manual 01-2024 (V204-1EN-03)
4.34 Mb
Image
VKV 280 EC - image 1
484 Kb
A B C
547 425 274