Vents VP 125 K Q

Centrifugal ceiling fans in steel casing with a plastic front panel
  • Maximum airflow: 225 m3/h
  • Sound pressure level LpA at 3 m: 43 dB(A)
  • Motor type: AC
  • Impeller type: Centrifugal backward curved blades
  • Casing material: Galvanized steel
Unit of measurement VP 125 K Q
Connected air duct size mm 125
Minimum supply voltage V 230
Maximum supply voltage V 230
Power supply frequency Hz 50/60
Rated power W 56
Unit current A 0.34
Maximum airflow m3/h 225
Sound pressure level LpA at 3 m dB(A) 43
Weight kg 3.4
Transported air temperature (max) °С 45
Transported air temperature (min) °С -25
Ingress protection rating - IPX4
Ingress protection rating of the drive - IP44
Vents VP 125 K Q 43 150 2016
Trademark Vents
Model VP 125 K Q
Specific energy consumption (SEC) (kWh/(m2/a)) Cold Average Warm
-51.5 A+ -24.4 C -8.9 F
Type of ventilation unit Unidirectional
Type of drive installed Variable speed
Type of heat recovery system None
Maximum flow rate (m3/h) 150
Electric power input (W) 56
Reference flow rate (m3/s) 0.029
Reference pressure difference (Pa) 50
Specific power input (SPI) (W/(m3/h)) 0.293
Control typology Local demand control
Maximum external leakage rates (%) 2.7
Declared typology RVU UVU
Sound power level (dB(A)) 43
The annual electricity consumption (AEC) (kWh/a) Cold Average Warm
155 155 155
The annual heating saved (AHS) (kWh/a) Cold Average Warm
5536 2830 1280
Datasheet
"VENTS VP" product description 05-2023
1.08 Mb
Manual
"VENTS VP" user's manual 09-2019 (V69EN-03)
7.57 Mb
BIM/CAD models
VP
2.14 Mb
Image
VP 125 K Q - image 1
302 Kb
∅D B H H1 L
125 240 160 189 305