Vents VUE 160 V1B EC A14

Air handling units in heat- and sound-insulated casing equipped with a counter-flow enthalpy heat exchanger
  • Maximum airflow: 200 m3/h
  • Sound pressure level LpA at 3 m: 22 dB(A)
  • Heat exchanger type: Counter flow
  • Extract filter: G4
  • Supply filter: F7 (G4 optional)
  • Sound insulation
  • Motor type: EC
  • Enthalpy heat exchanger
  • Bypass: Manual
  • Control: Remote Control
  • Casing material: Coated steel
  • Humidity sensor: Optional
  • CO2 sensor: Optional
  • VOC sensor: Optional
  • PM2.5 sensor: Optional
Unit of measurement VUE 160 V1B EC A14
Connected air duct size mm 125
Minimum supply voltage V 230
Maximum supply voltage V 230
Power supply frequency Hz 50/60
Rated power W 57
Unit current A 0.5
Maximum airflow m3/h 200
Sound pressure level LpA at 3 m dB(A) 22
Heat recovery efficiency, max % 92
Heat exchanger type - Counter flow
Heat exchanger material - Enthalpy
Weight kg 44
Extract filter - G4
Supply filter - F7 (G4 optional)
Transported air temperature (max) °С 40
Transported air temperature (min) °С -25
Ambient air temperature min °С 1
Ambient air temperature max °С 40
Ambient air humidity max % 60
Ingress protection rating - IP20
Ingress protection rating of the drive - IP44
Vents VUE 160 V1B EC A14 43 175 2016
Trademark Vents
Model VUE 160 V1B EC A14
Specific energy consumption (SEC) (kWh/(m2/a)) Cold Average Warm
-78.7 A+ -41.4 A -17.3 E
Type of ventilation unit Bidirectional
Type of drive installed Variable speed
Type of heat recovery system Recuperative
Thermal efficiency of heat recovery (%) 79
Maximum flow rate (m3/h) 175
Electric power input (W) 57
Reference flow rate (m3/s) 0.036
Reference pressure difference (Pa) 50
Specific power input (SPI) (W/(m3/h)) 0.215
Control typology Local demand control
Maximum internal leakage rates (%) 2.7
Maximum external leakage rates (%) 2.7
Declared typology RVU BVU
Sound power level (dB(A)) 43
The annual electricity consumption (AEC) (kWh/a) Cold Average Warm
696 159 114
The annual heating saved (AHS) (kWh/a) Cold Average Warm
8736 4466 2019
Datasheet
"VENTS VUT/VUE VB EC" product description 04-2024
3.79 Mb
Manual
"Sensor control panel A14/A15" user’s manual 07-2024 (V55-7EN-02)
1.21 Mb
Manual
"Modbus table for connecting A21 automation to BMS" user’s manual 09-2022 (V55-8-1EN-02)
167 Kb
Manual
"Wireless control system A21" user’s manual 02-2023 (V55-8EN-05)
504 Kb
Manual
"VENTS VUT/VUE 160/350/550 V(B) EC A14/A21" user's manual 09-2024 (V239EN-01)
3.22 Mb
Manual
"VENTS VUT/VUE 250 VB(E) EC L/R" user's manual 05-2024 (V240EN-04)
2.56 Mb
BIM/CAD models
VUT/VUE 250 VB(E) EC
1.26 Mb
BIM/CAD models
VUT/VUE 160/350/550 VB EC
1.28 Mb
Image
VUE 160 V1B EC A14 - image 1
453 Kb
ØD B H L
125 370 620 640
Name Photo Description
Vents HV2 HV2 Humidity sensor
Vents CO2-1 CO2-1 CO2 sensors
Vents CO2-2 CO2-2 CO2 sensors
Vents HR-S HR-S Electro-mechanical humidistats
Name Photo Description
Vents KH-1 KH-1 The kitchen exhaust hood is designed to clean air from combustion products, fumes, odors that form during cooking in the kitchen
Name Photo Description
Vents KRV 125 KRV 125 Air damper for air flow cut-off in round air ducts
Name Photo Description
Vents Belimo LF230 Belimo LF230 The Belimo LF series actuators are designed for controlling air dampers with cross section up to 0.8 m² performing protection functions
Other accessories
Name Photo Description
Vents SF 285x195x10 G4 SF 285x195x10 G4 Panel filter G4
Vents SF 285x195x10 F7 SF 285x195x10 F7 F7 panel filter