Unit of measurement | VUT 100 P mini | |||
Connected air duct size | mm | 125 | ||
Speed | - | 1 | 2 | 3 |
Minimum supply voltage | V | 230 | ||
Maximum supply voltage | V | 230 | ||
Power supply frequency | Hz | 50 | ||
Rated power | W | 56 | ||
Unit current | A | 0.34 | ||
Maximum airflow | m3/h | 55 | 74 | 100 |
Sound pressure level LpA at 3 m | dB(A) | 24 | 32 | 41 |
Heat recovery efficiency, max | % | 76 | ||
Heat exchanger type | - | Cross flow | ||
Heat exchanger material | - | Polystyrene | ||
Weight | kg | 13 | ||
Extract filter | - | G4 | ||
Supply filter | - | G4 | ||
Transported air temperature (max) | °С | 40 | ||
Transported air temperature (min) | °С | -25 | ||
Ambient air temperature min | °С | 1 | ||
Ambient air temperature max | °С | 40 | ||
Ambient air humidity max | % | 60 | ||
Ingress protection rating | - | IP22 | ||
Ingress protection rating of the drive | - | IP44 |
Trademark | Vents | |||||
Model | VUT 100 P mini | |||||
Specific energy consumption (SEC) (kWh/(m2/a)) | Cold | Average | Warm | |||
-54.1 | A+ | -22.3 | D | -1.5 | F | |
Type of ventilation unit | Bidirectional | |||||
Type of drive installed | Multi-speed | |||||
Type of heat recovery system | Recuperative | |||||
Thermal efficiency of heat recovery (%) | 68 | |||||
Maximum flow rate (m3/h) | 106 | |||||
Electric power input (W) | 56 | |||||
Reference flow rate (m3/s) | 0.021 | |||||
Reference pressure difference (Pa) | 50 | |||||
Specific power input (SPI) (W/(m3/h)) | 0.512 | |||||
Control typology | Manual control | |||||
Maximum internal leakage rates (%) | 2.7 | |||||
Maximum external leakage rates (%) | 2.7 | |||||
Declared typology | RVU BVU | |||||
Sound power level (dB(A)) | 61 | |||||
The annual electricity consumption (AEC) (kWh/a) | Cold | Average | Warm | |||
1224 | 687 | 642 | ||||
The annual heating saved (AHS) (kWh/a) | Cold | Average | Warm | |||
7592 | 3881 | 1755 |
Name | Photo | Description |
---|---|---|
Vents SR 125/600 | Silencer is applied for noise absorption produced during the ventilating equipment operation and spread along the ducting systems | |
Vents SR 125/900 | Silencer is applied for noise absorption produced during the ventilating equipment operation and spread along the ducting systems | |
Vents SR 125/1200 | Silencer is applied for noise absorption produced during the ventilating equipment operation and spread along the ducting systems | |
Vents SRF 125/600 | Silencer is applied for noise absorption produced during the ventilating equipment operation and spread along the ducting systems | |
Vents SRF 125/900 | Silencer is applied for noise absorption produced during the ventilating equipment operation and spread along the ducting systems | |
Vents SRF 125/2000 | Silencer is applied for noise absorption produced during the ventilating equipment operation and spread along the ducting systems |
Name | Photo | Description |
---|---|---|
Vents KOM 125 | Spring-loaded backdraft damper for round ducts | |
Vents KR 125 | Air damper for air flow control in round air ducts |
Name | Photo | Description |
---|---|---|
Vents SF 200x190x18 G4 | Panel filter G4 |