Unit of measurement | VUT 1000 PE EC | |
Connected air duct size | mm | 250 |
Phases | - | 1 |
Minimum supply voltage | V | 230 |
Maximum supply voltage | V | 230 |
Power supply frequency | Hz | 50/60 |
Rated power | W | 400 |
Power of electrical preheater | W | 0 |
Power of electrical reheater | W | 3300 |
Unit current | A | 16.56 |
Maximum airflow | m3/h | 1100 |
Sound pressure level LpA at 3 m | dB(A) | 52 |
Heat recovery efficiency, max | % | 90 |
Heat exchanger type | - | Counter flow |
Heat exchanger material | - | Aluminum |
Weight | kg | 95 |
Extract filter | - | G4 |
Supply filter | - | G4 |
Transported air temperature (max) | °С | 40 |
Transported air temperature (min) | °С | -25 |
Ambient air temperature min | °С | 1 |
Ambient air temperature max | °С | 40 |
Trademark | Vents |
Model | VUT 1000 PE EC |
Type of drive installed | Integrated VSD |
Type of heat recovery system | Recuperative |
Thermal efficiency of heat recovery (%) | 81 |
Nominal flow rate (m3/s) | 0.197 |
Nominal external pressure (Pa) | 314 |
Maximum internal leakage rates (%) | 2.7 |
Maximum external leakage rates (%) | 2.7 |
Static efficiency (%) | 59.9 |
Visual filter warning | See control panel catalogue data |
Effective electric power input (kW) | 0.379 |
Face velocity at design flow rate (m/s) | 1.111 |
Sound power level (dB(A)) | 72 |
Declared typology | NRVU BVU |
Energy perfomance of filters | B |
Name | Photo | Description |
---|---|---|
Vents SFK 647x274x27 G4 | G4 pocket filter | |
Vents SFK 647x274x27 F7 | F7 pocket filter | |
Vents SF 647x274x20 G4 | Panel filter G4 |
Name | Photo | Description |
---|---|---|
Vents SR 250/600 | Silencer is applied for noise absorption produced during the ventilating equipment operation and spread along the ducting systems | |
Vents SR 250/900 | Silencer is applied for noise absorption produced during the ventilating equipment operation and spread along the ducting systems | |
Vents SR 250/1200 | Silencer is applied for noise absorption produced during the ventilating equipment operation and spread along the ducting systems | |
Vents SRF 250/600 | Silencer is applied for noise absorption produced during the ventilating equipment operation and spread along the ducting systems | |
Vents SRF 250/900 | Silencer is applied for noise absorption produced during the ventilating equipment operation and spread along the ducting systems |
Name | Photo | Description |
---|---|---|
Vents KOM 250 | Spring-loaded backdraft damper for round ducts | |
Vents KRV 250 | Air damper for air flow cut-off in round air ducts |
Name | Photo | Description |
---|---|---|
Vents Belimo LF230 | The Belimo LF series actuators are designed for controlling air dampers with cross section up to 0.8 m² performing protection functions | |
Vents Belimo TF230 | The actuators are designed for controlling air dampers with cross section up to 0.4 m² performing protection functions |
Name | Photo | Description |
---|---|---|
Vents C 250 | The clamps are designed for quick and reliable mounting and connection of various round ventilation system components. Clamps are made of stainless and galvanized steel band |