Vents VUT 1500 EH

Vents VUT 1500 EH - Air handling units in sound-proof and heat-insulated casing with electric heater
Out of production
Air handling units in sound-proof and heat-insulated casing with electric heater
  • Power of electrical reheater: 18000 W
  • Maximum airflow: 1750 m3/h
  • Sound pressure level LpA at 3 m: 49 dB(A)
  • Heat exchanger type: Cross flow
  • Extract filter: G4
  • Supply filter: G4
  • Sound insulation
  • Motor type: AC
  • Reheater: Electric
  • Control: Remote Control
  • Casing material: Galvanized steel
Unit of measurement VUT 1500 EH
Connected air duct size mm 315
Minimum supply voltage V 230
Maximum supply voltage V 230
Power supply frequency Hz 50/60
Rated power W 980
Power of electrical reheater W 18000
Unit current A 30.3
Maximum airflow m3/h 1750
Sound pressure level LpA at 3 m dB(A) 49
Heat recovery efficiency, max % 77
Heat exchanger type - Cross flow
Heat exchanger material - Polystyrene
Weight kg 96
Extract filter - G4
Supply filter - G4
Transported air temperature (max) °С 40
Transported air temperature (min) °С -25
Ambient air temperature min °С 1
Ambient air temperature max °С 40
Ambient air humidity max % 80
Ingress protection rating - IP22
Ingress protection rating of the drive - IP44
Trademark Vents
Model VUT 1500 EH
Type of drive installed Integrated MSD
Type of heat recovery system Recuperative
Thermal efficiency of heat recovery (%) 67
Nominal flow rate (m3/s) 0.194
Nominal external pressure (Pa) 239
Maximum internal leakage rates (%) 2.7
Maximum external leakage rates (%) 2.7
Static efficiency (%) 33.4
Visual filter warning See control panel catalogue data
Effective electric power input (kW) 0.59
Face velocity at design flow rate (m/s) 0.913
Sound power level (dB(A)) 69
Declared typology NRVU BVU
Energy perfomance of filters B
Datasheet
"VENTS VUT EH, VENTS VUT WH" product description 01-2023
4.06 Mb
Manual
"VENTS VUT EH" user's manual 06-2021 (V28EN-06)
2.93 Mb
Image
VUT 1500 EH - image 1
770 Kb
Vents VUT 1500 EH - Dimensions
ØD B B1 B2 B3 H H1 H2 H3 L L1 L2
314 842 581 320 520 814 947 201 595 1345 1388 1445
Name Photo Description
Vents SR 315/600 SR 315/600 Silencer is applied for noise absorption produced during the ventilating equipment operation and spread along the ducting systems
Vents SR 315/900 SR 315/900 Silencer is applied for noise absorption produced during the ventilating equipment operation and spread along the ducting systems
Vents SR 315/1200 SR 315/1200 Silencer is applied for noise absorption produced during the ventilating equipment operation and spread along the ducting systems
Vents SRF 315/600 SRF 315/600 Silencer is applied for noise absorption produced during the ventilating equipment operation and spread along the ducting systems
Vents SRF 315/900 SRF 315/900 Silencer is applied for noise absorption produced during the ventilating equipment operation and spread along the ducting systems
Vents SRF 315/2000 SRF 315/2000 Silencer is applied for noise absorption produced during the ventilating equipment operation and spread along the ducting systems
Name Photo Description
Vents KOM 315 KOM 315 Spring-loaded backdraft damper for round ducts
Vents KR 315 KR 315 Air damper for air flow control in round air ducts
Other accessories
Name Photo Description
Vents SF 780x273x48 G4 SF 780x273x48 G4 Panel filter G4
Vents VL C4 300/384 VL C4 300/384 Summer block