Unit of measurement | VUT 180 P5B EC A21 | |
Connected air duct size | mm | 150 |
Minimum supply voltage | V | 230 |
Maximum supply voltage | V | 230 |
Power supply frequency | Hz | 50/60 |
Rated power | W | 87 |
Unit current | A | 0.71 |
Maximum airflow | m3/h | 220 |
Sound pressure level LpA at 3 m | dB(A) | 33 |
Heat recovery efficiency, max | % | 98 |
Heat exchanger type | - | Counter flow |
Heat exchanger material | - | Polystyrene |
Weight | kg | 14 |
Extract filter | - | G4 |
Supply filter | - | G4, F7 |
Transported air temperature (max) | °С | 40 |
Transported air temperature (min) | °С | -25 |
Ambient air temperature min | °С | 1 |
Ambient air temperature max | °С | 40 |
Ambient air humidity max | % | 60 |
Ingress protection rating | - | IP22 |
Ingress protection rating of the drive | - | IP44 |
ØD | ØD1 | B | B2 | H | H1 | H2 | L | L1 |
---|---|---|---|---|---|---|---|---|
150 | 19 | 600 | 326 | 264 | 38 | 302 | 900 | 1009 |
Name | Photo | Description |
---|---|---|
Vents A25 | The control panel with a sensor display | |
Vents A22 | The A22/A22 WiFi control panels are used for control of industrial and domestic air handling units with an A21 automation system. | |
Vents A22 WiFi | The A22/A22 WiFi control panels are used for control of industrial and domestic air handling units with an A21 automation system. |
Name | Photo | Description |
---|---|---|
Vents HV2 | Humidity sensor | |
Vents CO2-1 | CO2 sensors | |
Vents CO2-2 | CO2 sensors | |
Vents HR-S | Electro-mechanical humidistats | |
Vents DPWC11200 | Humidity sensor |
Name | Photo | Description |
---|---|---|
Vents DPWQ30600 | VOC sensors | |
Vents DPWQ40200 | CO2 sensor |
Name | Photo | Description |
---|---|---|
Vents NKD 150-0,8-1 A21 V.2 | Duct heater for supply air post-heating with external control | |
Vents NKD 150-1,2-1 A21 V.2 | Duct heater for supply air post-heating with external control | |
Vents NKD 150-1,7-1 A21 V.2 | Duct heater for supply air post-heating with external control | |
Vents NKD 150-2,0-1 A21 V.2 | Duct heater for supply air post-heating with external control | |
Vents NKP 150-0,8-1 A21 V.2 | Heater for heat exchanger freeze protection | |
Vents NKP 150-1,2-1 A21 V.2 | Heater for heat exchanger freeze protection | |
Vents NKP 150-1,7-1 A21 V.2 | Heater for heat exchanger freeze protection | |
Vents NKP 150-2,0-1 A21 V.2 | Heater for heat exchanger freeze protection |
Name | Photo | Description |
---|---|---|
Vents SH-32 | The hydraulic U-trap for condensate drainage from heat exchangers and coolers in ventilation and air conditioning systems |
Name | Photo | Description |
---|---|---|
Vents KRV 150 | Air damper for air flow cut-off in round air ducts |
Name | Photo | Description |
---|---|---|
Vents Belimo LF230 | The Belimo LF series actuators are designed for controlling air dampers with cross section up to 0.8 m² performing protection functions |
Name | Photo | Description |
---|---|---|
Vents SF 214x186x18 G4 | Panel filter G4 | |
Vents SF 214x186x48 F7 | F7 panel filter |