VENTS VUT 2000 WH-4

  • Description
  • Characteristics
  • Downloads
  • Dimensions
  • Additional diagrams
  • Legend
Description
Description
DESCRIPTION MODIFICATIONS
  • Air handling units VUT WH with water heater are the complete air handling units designed to provide both supply and exhaust ventilation with air filtering and heat recovery.
  • The exhaust air energy is used to heat up the supply fresh air through the heat exchanger.
  • All the models are designed for connection with Ø 125, 150, 160, 200, 250, 315 mm round ducts.
  • VUT WH – a range of compact energy saving air handling units (AHU) equipped with supply and exhaust centrifugal fans, cross-flow heat recovery elements, water or glycol heating coils and air filters.

FILTER
  • Two incorporated G4 panel filters for extract air ventilation and F7 filters for supply air ventilation are supplied with the unit.

FANS CASING
  • The units are equipped with supply and exhaust centrifugal double-inlet fans with forward curved blades and built-in thermostat with automatic restart.
  • The electric motors and impellers are dynamically balanced in two planes.
  • The ball-bearings used with motors are designed for at least 40 000 hours operation and are maintenance-free.
  • The casing is manufactured from aluminum-zinc compound with 25 mm thick mineral wool heat- and sound-insulating layer.
HEAT EXHANGER
  • The heat exchangers have high efficiency and are manufactured from aluminium plates. The unit is also equipped with the drain pan for condensate drainage.

HEATER  
  • The water heater at outlet from the heat exchanger is designed for warming up of supply air up to the set level if heat recovery is not enough to attain the set supply air temperature.
  • The water heaters are designed for max. operating pressure 1.0 MPa (10 bar) and max. heat medium operating temperature 95 °C.
AUTOMATION AND CONTROL SYSTEM  
  • The unit incorporates an integrated automation and control system with a multi-functional control panel with LCD display.
  • The standard delivery set includes 10 m connection cable for connection to the remote control panel.
  • The unit has the freezing protection function to prevent the heat exchanger freezing by means of actuating the bypass damper and controlling water heater.
  • As the temperature sensor warns of the freezing danger, the bypass air damper is opened and the intake air is directed through the air duct beside the heat exchanger.
  • As the heat exchanger is warmed the supply air temperature rises up to the set level while passing through the heater.
  • Meanwhile the warm extract air warms up the heat exchanger. After the freezing danger is no longer imminent, the bypass damper shuts the bypass duct and the unit reverts to the standard operation mode.
VUT WH CONTROL AND PROTECTION FUNCTIONS  
  • control from the control panel: switching on/off, three-speed fan selection, selecting heating/cooling modes (if connected to duct heater); room temperature display;
  • maintaining supply air temperature set from the control panel by controlling the circulation pump and actuating the heat medium regulating valve; input from the heat medium flow switch (pump alarm);
  • safe start-up/ shutdown of the fans, warming up of the water heater before start-up; return heat medium temperature control when the fan is off;
  • freezing protection of the water heating coils by the exhaust temperature sensor and the return heat medium temperature sensor;
  • control of the compressor and condensing unit of the water cooler by the room temperature sensor (for the models equipped with a duct air cooler);
  • actuating the external air dampers with a return spring;
  • unit operation according to week schedule (set at the system setup);
  • unit shut down at signal from the fire alarm system;
  • smooth bypass damper control in the bypassing mode to prevent the heat exchanger freezing.
ACCESSORIES FOR AIR HANDLING UNITS:  

SF

Type Replaceable filter (panel filter) G4 Replaceable filter (panel filter) F7
VUT 800 WH-2 SF VUT 1000 EH/WH G4 SF VUT 1000 EH/WH F7
VUT 800 WH-4
VUT 1000 WH-2
VUT 1000 WH-4
VUT 1500 WH-2 SF VUT 2000 EH/WH G4 SF VUT 2000 EH/WH F7
VUT 1500 WH-4
VUT 2000 WH-2
VUT 2000 WH-4
 
MOUNTING
 
  • The unit is designed for indoor mounting. While mounting the unit provide the correct condensate collection and drainage.
  • Access for the unit servicing and filter cleaning is from the side panels on the left from supply air side. 
  • Access for the unit servicing for VUT 1500 WH and VUT 2000 WH is available from the left or right side panels depends on order code.
OPTIONS  
  • For attenuation of sound generated by the fans it is recommended to install the duct silencer (refer SR) from inside before the unit.
  • For vibration absorbing it is recommended to install the flexible antivibration connectors (refer VVG) on both sides of the unit.
  • The mixing units USWK are recommended for smooth supply air temperature regulation in the units equipped with water heaters.
  • The mixing unit USWK with three-way heat medium regulating valve and circulation pump provides smooth heating capacity regulation and minimizes the water heater freezing danger.
Characteristics
Characteristics
Parameter VUT 2000 WH-4
Measurement unit
Heating water heating -
Frequency 50 Hz
Engine Type 220В / 50Гц -
Phase 1 ˜
Voltage 220-240 V
Maximum fan power Maximum fan power 2шт. х 650 W
Air capacity 2100 m³/h
Maximum air capacity 2100 m³/h
Total unit power 1300 W
Total unit current 5.68 A
Fan current Fan current 2шт. х 2.84 A
RPM 1150 min-1
Heat recovery efficiency 78 -
Noize level at 3 m 65 dBА
Casing material aluzinc -
Maximum transported air temperature Maximum transported air temperature -25 +40 °С
Insulation 50 mm, mineral wool -
Filter: extract G4 -
Filter: supply * option G4 (F7*) -
Connected air duct diameter 315 mm
Number of water (glycol) coil rows 4 -
Mass 99 kg
SEC Class - -
Heater type Heater type water -
Connection diameter 315 mm
Heat recovery efficiency Heat recovery efficiency 77 %
Heat exchanger type cross-flow -
Heat exchanger material алюминий -
Duct connection Duct connection горизонтальное -
Type Type приточно-вытяжная с рекуперацией -
Heat recovery Heat recovery 1 -
Mounting floor mounting -
Files archieve
Downloads
Name
Download high quality image "VENTS VUT WH (ErP 2016)" (psd 4.49Mb)
Brochure "VENTS VUT EH/ WH" (pdf 880.01Kb)
User's manual "Control system for air supply and air handling units based on Freemax controllers and AC208A2 sensor control panels" (pdf 1.38Mb)
User's manual "VENTS VUT WH" (pdf 2.49Mb)
Download image "VENTS VUT WH (ErP 2016)" for your website (png 441.04Kb)
Dimensions
Characteristics
VENTS  VUT 2000 WH-4
Parameter Value Measurement unit
B 842 mm
B1 581 mm
B2 320 mm
B3 520 mm
H 814 mm
H1 947 mm
H2 201 mm
H3 595 mm
L 1345 mm
L1 1388 mm
Additional diagrams
Additional diagrams
Sound-power level   Octave-frequency band [Hz]
  Hz   General   63   125   250   500   1000   2000   4000   8000
LwA to inlet   dBA 76 82 81 77 69 72 68 65 60
LwA to outlet dBA 79 86 80 79 74 75 70 74 68
LwA to environment dBA 58 66 64 58 51 48 45 41 38

Legend
Legend
Series   Rated air capacity [m3/h]   Heater type   Duct connection   Row number of the
heater
  Service side (for VUT 1500 WH, VUT 2000 WH)
VENTS VUT
  800; 1000; 1500; 2000   W - water   H - horizontal   2 – two rows;
4 –
four rows
  L– left side
R – right side