Vents VUT 530 H

Air handling units in the compact sound- and heat-insulated casing
  • Maximum airflow: 530 m3/h
  • Sound pressure level LpA at 3 m: 48 dB(A)
  • Heat exchanger type: Cross flow
  • Extract filter: G4
  • Supply filter: G4
  • Sound insulation
  • Motor type: AC
  • Control: Remote Control
  • Casing material: Galvanized steel
Unit of measurement VUT 530 H
Connected air duct size mm 249
Minimum supply voltage V 230
Maximum supply voltage V 230
Power supply frequency Hz 50/60
Rated power W 300
Unit current A 1.32
Maximum airflow m3/h 530
Sound pressure level LpA at 3 m dB(A) 48
Heat recovery efficiency, max % 88
Heat exchanger type - Cross flow
Heat exchanger material - Polystyrene
Weight kg 49
Extract filter - G4
Supply filter - G4
Transported air temperature (max) °С 40
Transported air temperature (min) °С -25
Ambient air temperature min °С 10
Ambient air temperature max °С 50
Ambient air humidity max % 80
Ingress protection rating - IP22
Ingress protection rating of the drive - IP44
Vents VUT 530 H 57 470 2016
Trademark Vents
Model VUT 530 H
Specific energy consumption (SEC) (kWh/(m2/a)) Cold Average Warm
-48.8 A+ -18.2 E 1.9 G
Type of ventilation unit Bidirectional
Type of drive installed Multi-speed
Type of heat recovery system Recuperative
Thermal efficiency of heat recovery (%) 64
Maximum flow rate (m3/h) 470
Electric power input (W) 300
Reference flow rate (m3/s) 0.091
Reference pressure difference (Pa) 50
Specific power input (SPI) (W/(m3/h)) 0.578
Control typology Manual control
Maximum internal leakage rates (%) 2.7
Maximum external leakage rates (%) 2.7
Declared typology RVU BVU
Sound power level (dB(A)) 57
The annual electricity consumption (AEC) (kWh/a) Cold Average Warm
1336 799 754
The annual heating saved (AHS) (kWh/a) Cold Average Warm
7343 3754 1697
Datasheet
"VENTS VUT H" product description 01-2023
1.33 Mb
Manual
"VENTS VUT H" user's manual 10-2019 (V26EN-04)
2.38 Mb
Certificates
Certificate LVD "VUT H"
230 Kb
Certificates
Certificate GS "VUT H"
229 Kb
Certificates
Declaration of сonformity "VUT H"
1.65 Mb
Image
VUT 530 H - image 1
511 Kb
ØD B B1 B2 B3 H H1 H2 L L1
159 416 300 54 207 603 230 148 722 768
Name Photo Description
Vents SR 160/600 SR 160/600 Silencer is applied for noise absorption produced during the ventilating equipment operation and spread along the ducting systems
Vents SR 160/900 SR 160/900 Silencer is applied for noise absorption produced during the ventilating equipment operation and spread along the ducting systems
Vents SR 160/1200 SR 160/1200 Silencer is applied for noise absorption produced during the ventilating equipment operation and spread along the ducting systems
Vents SRF 160/600 SRF 160/600 Silencer is applied for noise absorption produced during the ventilating equipment operation and spread along the ducting systems
Vents SRF 160/900 SRF 160/900 Silencer is applied for noise absorption produced during the ventilating equipment operation and spread along the ducting systems
Vents SRF 160/2000 SRF 160/2000 Silencer is applied for noise absorption produced during the ventilating equipment operation and spread along the ducting systems
Name Photo Description
Vents KOM 160 KOM 160 Spring-loaded backdraft damper for round ducts
Vents KR 160 KR 160 Air damper for air flow control in round air ducts
Other accessories
Name Photo Description
Vents SF 378x210x48 G4 SF 378x210x48 G4 Panel filter G4
Vents VL C4 300/384 VL C4 300/384 Summer block