Unit of measurement | VUTR 650 PE EC R A21 | |
Connected air duct size | mm | 200 |
Minimum supply voltage | V | 230 |
Maximum supply voltage | V | 230 |
Power supply frequency | Hz | 50/60 |
Rated power | W | 367 |
Power of electrical reheater | W | 2800 |
Unit current | A | 13.7 |
Maximum airflow | m3/h | 710 |
Sound pressure level LpA at 3 m | dB(A) | 36 |
Heat recovery efficiency, max | % | 87 |
Heat exchanger type | - | Rotary |
Heat exchanger material | - | Aluminum |
Weight | kg | 104 |
Extract filter | - | G4 |
Supply filter | - | G4, F7 (H13 option) |
Transported air temperature (max) | °С | 40 |
Transported air temperature (min) | °С | -25 |
Ambient air temperature min | °С | 1 |
Ambient air temperature max | °С | 40 |
Ambient air humidity max | % | 80 |
Ingress protection rating | - | IP22 |
Ingress protection rating of the drive | - | IP44 |
Trademark | Vents | |||||
Model | VUTR 650 PE EC R A21 | |||||
Specific energy consumption (SEC) (kWh/(m2/a)) | Cold | Average | Warm | |||
85.4 | A+ | 41.9 | A | 17 | E | |
Type of ventilation unit | Bidirectional | |||||
Type of drive installed | Variable speed | |||||
Type of heat recovery system | Regenerative | |||||
Thermal efficiency of heat recovery (%) | 83 | |||||
Maximum flow rate (m3/h) | 650 | |||||
Electric power input (W) | 340 | |||||
Reference flow rate (m3/s) | 0.125 | |||||
Reference pressure difference (Pa) | 50 | |||||
Specific power input (SPI) (W/(m3/h)) | 0.269 | |||||
Control typology | Local demand control | |||||
Maximum internal leakage rates (%) | 2.7 | |||||
Maximum external leakage rates (%) | 2.7 | |||||
Sound power level (dB(A)) | 55 | |||||
Declared typology | RVU BVU | |||||
The annual electricity consumption (AEC) (kWh/a) | Cold | Average | Warm | |||
142 | 142 | 142 | ||||
The annual heating saved (AHS) (kWh/a) | Cold | Average | Warm | |||
8898 | 4548 | 2057 |
ØD | ØD1 | B | H | L | L1 |
---|---|---|---|---|---|
200 | 125 | 932 | 422 | 1445 | 1542 |
Name | Photo | Description |
---|---|---|
Vents A25 | The control panel with a sensor display | |
Vents A22 | The A22/A22 WiFi control panels are used for control of industrial and domestic air handling units with an A21 automation system. | |
Vents A22 WiFi | The A22/A22 WiFi control panels are used for control of industrial and domestic air handling units with an A21 automation system. |
Name | Photo | Description |
---|---|---|
Vents DPWQ30600 | VOC sensors | |
Vents DPWQ40200 | CO2 sensor |
Name | Photo | Description |
---|---|---|
Vents DPWC11200 | Humidity sensor | |
Vents HR-S | Electro-mechanical humidistats | |
Vents HV2 | Humidity sensor |
Name | Photo | Description |
---|---|---|
Vents KOM 200 | Spring-loaded backdraft damper for round ducts | |
Vents KRV 200 | Air damper for air flow cut-off in round air ducts |
Name | Photo | Description |
---|---|---|
Vents Belimo LF230 | The Belimo LF series actuators are designed for controlling air dampers with cross section up to 0.8 m² performing protection functions | |
Vents Belimo TF230 | The actuators are designed for controlling air dampers with cross section up to 0.4 m² performing protection functions |
Name | Photo | Description |
---|---|---|
Vents SF 378x295x48 G4 | Panel filter G4 | |
Vents SF 378x295x48 F7 | F7 panel filter |
Name | Photo | Description |
---|---|---|
Vents KH-1 | The kitchen exhaust hood is designed to clean air from combustion products, fumes, odors that form during cooking in the kitchen |