Series Vents JAF 60 Hz

Axial jet fans for ventilation of parkings. Transported air temperature in continuous mode up to +55°C, in smoke extraction mode: 300 °C/2 h, 400 °C/2 h. Functionality. Power. Efficiency.
Application

JAF jet axial fans are designed for general purpose ventilation of underground and semi-opened parkings, ventilation of tunnels, smoke extraction in case of fire as a part of smoke extract system. The fans generate a high-speed and high-pressure directed air jet.


Modifications
  • Unidirectional single-speed type (U).
  • Unidirectional double-speed type (U).
  • Reversible single-speed (R).
  • Reversible double-speed (R).


Design

JAF casing has a tubular shape and is made of polymer coated steel. There are two models available for order - with cylindrical or octagonal casing. The fan with octagonal casing has lower dimensions in height, a hinged hatch for electrical installation with captive bolts, and a removable middle part for technical service. The fan has a sound insulation of mineral wool. The casing includes inner brackets for motor fixation. These brackets act as directing vanes and distribute air flow uniformly, thus increasing aerodynamic performances of the fan.

Motor

A three-phase asynchronous motor with a short-circuit rotor is installed in the fan casing. The motor ingress protection rating is IP55. The motor design ensures operation of the fan in the smoke extract systems or/and in the general ventilation systems on unidirectional and reverse modes. The motors are rated for 400 V power mains voltage and 60 Hz frequency.


Impeller

Dynamically balanced impeller made of cast aluminium alloy for smoke extraction fans and of reinforced fiberglass polyamide for general ventilation fans. The reversible fans are equipped with 100 % reversible two-directional impeller.


Mounting

JAF fans are designed for horizontal ceiling mounting and fixation by means of the supplied fixing brackets attached to the fan casing.


Reference

The fans with octagonal casing can be ordered only in 315, 355, and 400 diameters.

The fans with the fire resistance limit 200 °C/2 h can be manufactured on special request

JAF-CI axial jet fan design

JAF-VI axial jet fan design
Lineup Vents JAF 60 Hz
Datasheet
"JAF (60 Hz)" product description 05-2021
1.01 Mb
BIM/CAD models
RFA models "JAF"
6.63 Mb
Certificates
BSI certificate 0086 CPR 784743 "Vents ICF, JAF-CI, VDO, VDKO"
1.14 Mb
Certificates
BSI certificate 2797 CPR 692414 "Vents ICF, JAF-CI, VDO, VDKO"
1.21 Mb
Image
JAF 60 Hz - image 1
476 Kb