Unit of measurement | Enave-C 150 P A21 | |
Connected air duct size | mm | 160/125 |
Phases | - | 1 |
Minimum supply voltage | V | 230 |
Maximum supply voltage | V | 230 |
Power supply frequency | Hz | 50/60 |
Rated power | W | 72 |
Unit current | A | 0.63 |
Maximum airflow | m3/h | 229 |
Sound pressure level LpA at 3 m | dB(A) | 27 |
Heat recovery efficiency, max | % | 89 |
Heat exchanger type | - | Counter flow |
Heat exchanger material | - | Polystyrene |
Weight | kg | 18 |
Extract filter | - | G4 / Coarse > 60% |
Supply filter | - | G4 / Coarse > 60% (option F7 / ePM1 60%) |
Transported air temperature (max) | °С | 45 |
Ambient air temperature min | °С | 1 |
Ambient air temperature max | °С | 40 |
Ambient air humidity max | % | 60 |
Ingress protection rating | - | IP22 |
Ingress protection rating of the drive | - | IP44 |
Trademark | Vents | |||||
Model | Enave-C 150 P A21 | |||||
Specific energy consumption (SEC) (kWh/(m2/a)) | Cold | Average | Warm | |||
-81.6 | A+ | -43.1 | A+ | -18.4 | E | |
Type of ventilation unit | Bidirectional | |||||
Type of drive installed | Variable speed | |||||
Type of heat recovery system | Recuperative | |||||
Thermal efficiency of heat recovery (%) | 85 | |||||
Maximum flow rate (m3/h) | 168 | |||||
Electric power input (W) | 64 | |||||
Reference flow rate (m3/s) | 0.033 | |||||
Reference pressure difference (Pa) | 50 | |||||
Specific power input (SPI) (W/(m3/h)) | 0.18 | |||||
Control typology | Local demand control | |||||
Maximum internal leakage rates (%) | 2.7 | |||||
Maximum external leakage rates (%) | 2.7 | |||||
Sound power level (dB(A)) | 48 | |||||
The annual electricity consumption (AEC) (kWh/a) | Cold | Average | Warm | |||
677 | 140 | 95 | ||||
The annual heating saved (AHS) (kWh/a) | Cold | Average | Warm | |||
8979 | 4590 | 2075 |
Name | Photo | Description |
---|---|---|
Vents SF 200x165x48 Coarse 90% G4 |
![]() |
Panel filter G4 |
Vents SF 200x165x48 ePM1 65% F7 |
![]() |
F7 panel filter |
Name | Photo | Description |
---|---|---|
Vents A25 |
![]() |
Touch screen control panel for controlling industrial and residential air handling units |
Vents A22 |
![]() |
Control panels for controlling industrial and residential air handling units |
Vents A22 WiFi |
![]() |
Control panels for controlling industrial and residential air handling units |
Name | Photo | Description |
---|---|---|
Vents HV2 |
![]() |
Humidity sensor |
Vents CO2-3 |
![]() |
CO2 sensor |
Vents CO2-1 |
![]() |
CO2 sensors |
Vents CO2-2 |
![]() |
CO2 sensors |
Vents HR-S |
![]() |
Electro-mechanical humidistat |
Name | Photo | Description |
---|---|---|
Vents NKP 160-0,8-1 A21 V.2 |
![]() |
Inline heaters for heat exchanger frost protection |
Vents NKP 160-1,2-1 A21 V.2 |
![]() |
Inline heaters for heat exchanger frost protection |
Vents NKP 160-1,7-1 A21 V.2 |
![]() |
Inline heaters for heat exchanger frost protection |
Vents NKP 160-2,0-1 A21 V.2 |
![]() |
Inline heaters for heat exchanger frost protection |
Vents NKD 160-0,8-1 A21 V.2 |
![]() |
Inline supply air reheaters with external control |
Vents NKD 160-1,2-1 A21 V.2 |
![]() |
Inline supply air reheaters with external control |
Vents NKD 160-1,7-1 A21 V.2 |
![]() |
Inline supply air reheaters with external control |
Vents NKD 160-2,0-1 A21 V.2 |
![]() |
Inline supply air reheaters with external control |
Name | Photo | Description |
---|---|---|
Vents SH-32 |
![]() |
Hydraulic U-trap to drain condensate from heat exchangers and coolers |
Name | Photo | Description |
---|---|---|
Vents SR 160/600 |
![]() |
Silencers made of galvanized steel filled with non-combustible sound-absorbing material |
Vents SR 160/900 |
![]() |
Silencers made of galvanized steel filled with non-combustible sound-absorbing material |
Vents SR 160/1200 |
![]() |
Silencers made of galvanized steel filled with non-combustible sound-absorbing material |
Name | Photo | Description |
---|---|---|
Vents KRV 160 |
![]() |
Air dampers for automatic air flow control in round ducts |
Name | Photo | Description |
---|---|---|
Vents Belimo TF230 |
![]() |
The actuators are designed for controlling air dampers with cross section up to 0.4 m² performing protection functions |