Vents KSB 160 K2

Inline centrifugal fans in heat- and sound-insulated casing
  • Maximum airflow: 500 m3/h
  • Sound pressure level LpA at 3 m: 38 dB(A)
  • Sound insulation
  • Motor type: AC
  • Impeller type: Centrifugal backward curved blades
  • Casing material: Aluzinc
  • Installation in any position
Unit of measurement KSB 160 K2
Connected air duct size mm 160
Phases - 1
Minimum supply voltage V 230
Maximum supply voltage V 230
Power supply frequency Hz 50
Rated power W 86
Unit current A 0.38
Maximum airflow m3/h 500
rotation speed at 50hz - 2670
Sound pressure level LpA at 3 m dB(A) 38
Weight kg 17
Transported air temperature (max) °С 55
Transported air temperature (min) °С -25
Ingress protection rating - IPX4
Ingress protection rating of the drive - IP44
Vents KSB 160 K2 58 430 2018
Trademark Vents
Model KSB 160 K2
Specific energy consumption (SEC) (kWh/(m2/a)) Cold Average Warm
51.7 A+ 24.6 C 9.1 F
Type of ventilation unit Unidirectional
Type of drive installed Variable speed
Type of heat recovery system None
Maximum flow rate (m3/h) 430
Electric power input (W) 82
Reference flow rate (m3/s) 0.084
Reference pressure difference (Pa) 50
Specific power input (SPI) (W/(m3/h)) 0.278
Control typology Local demand control
Maximum external leakage rates (%) 2.7
Declared typology RVU UVU
Sound power level (dB(A)) 58
The annual electricity consumption (AEC) (kWh/a) Cold Average Warm
147 147 147
The annual heating saved (AHS) (kWh/a) Cold Average Warm
5536 2830 1280
Datasheet
"VENTS KSB K2" product description 05-2024
1.18 Mb
Manual
"VENTS KSB K2" user’s manual 04-2024 (V143-1EN-03)
2.46 Mb
BIM/CAD models
KSB K2 (EC)
2.3 Mb
Image
KSB 160 K2 - image 1
287 Kb
Vents KSB 160 K2 - Dimensions
∅D B B1 H L L1 L2
159 470 278 282 566 586 493