Unit of measurement | Micra 100 ERV | |||
Connected air duct size | mm | 100 | ||
Minimum supply voltage | V | 110 | ||
Maximum supply voltage | V | 240 | ||
Power supply frequency | Hz | 50/60 | ||
Rated power | W | 12 | 21 | 45 |
Unit current | A | 0.4 | ||
Maximum airflow | m3/h | 30 | 60 | 100 |
Sound pressure level LpA at 3 m | dB(A) | 13 | 27 | 39 |
Heat recovery efficiency | % | 96 | 89 | 83 |
Heat exchanger type | - | Counter flow | ||
Heat exchanger material | - | Enthalpy | ||
Weight | kg | 31 | ||
Extract filter | - | G4 | ||
Supply filter | - | G4 (option: F7) | ||
Transported air temperature (max) | °С | 40 | ||
Transported air temperature (min) | °С | -20 | ||
Ambient air temperature min | °С | 1 | ||
Ambient air temperature max | °С | 40 | ||
Ambient air humidity max | % | 70 | ||
Ingress protection rating | - | IP22 | ||
Ingress protection rating of the drive | - | IP44 |
Trademark | Vents | |||||
Model | Micra 100 ERV | |||||
Specific energy consumption (SEC) (kWh/(m2/a)) | Cold | Average | Warm | |||
-78.7 | A+ | -40.3 | A | -15.6 | E | |
Type of ventilation unit | Bidirectional | |||||
Type of drive installed | Variable speed | |||||
Type of heat recovery system | Recuperative | |||||
Thermal efficiency of heat recovery (%) | 86 | |||||
Maximum flow rate (m3/h) | 100 | |||||
Electric power input (W) | 45 | |||||
Reference flow rate (m3/s) | 0.017 | |||||
Specific power input (SPI) (W/(m3/h)) | 0.35 | |||||
Control typology | Local demand control | |||||
Maximum internal leakage rates (%) | 0.1 | |||||
Maximum external leakage rates (%) | 0.9 | |||||
Mixing rate (%) | 1 | |||||
Airflow sensitivity at +20 Pa and -20 Pa (%) | 0.93 | |||||
The indoor/outdoor air tightness (m3/h) | 7 | |||||
Declared typology | RVU BVU | |||||
Sound power level (dB(A)) | 47 | |||||
The annual electricity consumption (AEC) (kWh/a) | Cold | Average | Warm | |||
786 | 249 | 204 | ||||
The annual heating saved (AHS) (kWh/a) | Cold | Average | Warm | |||
8963 | 4581 | 2072 |
Name | Photo | Description |
---|---|---|
Vents MK Micra 100 white | Mounting kit: Two plastic air ducts; Outdoor box; Cardboard template | |
Vents MK Micra 100 chrome | Mounting kit: Two plastic air ducts; Outdoor box; Cardboard template | |
Vents NB Micra 100 white | Outdoor box | |
Vents NB Micra 100 chrome | Outdoor box | |
Vents NE Micra 100 | Heater to prevent condensate freezing in the drain pipe and the outdoor box | |
Vents SF 193x158x18 G4 | Panel filter G4 | |
Vents SF 193x158x47 F8 | F8 panel filter | |
Vents SF 193x158x47 F8 C | F8 carbon filter | |
Vents SF 193x158x47 H13 | H13 HEPA filter | |
Vents VL R6 366/157 | Summer block | |
Vents SF 193x158x47 F7 | F7 panel filter |
Name | Photo | Description |
---|---|---|
Vents HR-S | Electro-mechanical humidistats | |
Vents CO2-1 | CO2 sensors | |
Vents CO2-2 | CO2 sensors |