Vents VKH 2E 250

Roof centrifugal fans with horizontal air discharge
  • Sound pressure level LpA at 3 m: 54 dB(A)
  • Impeller type: Centrifugal impeller with backward curved blades
  • Casing material: Coated steel
Unit of measurement VKH 2E 250
Phases - 1
Maximum supply voltage V 230
Minimum supply voltage V 230
Power supply frequency Hz 50/60
Rated power W 184
Unit current A 0.81
Maximum airflow m³/h 1450
Rotation speed at 50hz - 2480
Sound pressure level LpA at 3 m dB(A) 54
Weight kg 12.7
Transported air temperature (max) °С 50
Transported air temperature (min) °С -25
Ingress protection rating - IPX4
Ingress protection rating of the drive - IP44
Impeller material - Plastic
Size mm 250
Trademark Vents
Model VKH 2E 250
Type of drive installed External MSD or VSD
Type of heat recovery system None
Nominal external pressure (Pa) 211
Maximum external leakage rates (%) 2.7
Static efficiency (%) 20.1
Effective electric power input (kW) 0.208
Sound power level (dB(A)) 85
Declared typology NRVU UVU
Datasheet
"VENTS VKV, VKH" product description 10-2025
1.93 Mb
Manual
"VENTS VKV, VKH" user's manual 11-2025 (V204EN-02)
6.12 Mb
Image
VKH 2E 250 - image 1
382 Kb
H H1 A B C Ød ØD
237 244 451 450 330 11 285
Name Photo Description
Vents RKV 250-315 RKV 250-315 Mounting frame
Vents RKVI 250-315 RKVI 250-315 Mounting frame with thermal-insulating layer
Vents FKV 250-315 FKV 250-315 Mating flange
Vents GKV 250-315 GKV 250-315 Flexible connector
Vents KKV 250-315 KKV 250-315 Backdraft damper