Vents VKMK 250

Roof centrifugal fans
  • Sound pressure level LpA at 3 m: 52 dB(A)
  • Impeller type: Centrifugal impeller with backward curved blades
  • Casing material: Coated steel
Unit of measurement VKMK 250
Connected air duct size mm 250
Phases - 1
Minimum supply voltage V 220
Maximum supply voltage V 240
Power supply frequency Hz 50/60
Rated power W 194
Unit current A 0.85
Maximum airflow m³/h 1310
Rotation speed at 50hz - 2790
Sound pressure level LpA at 3 m dB(A) 52
Weight kg 10.1
Transported air temperature (max) °С 50
Transported air temperature (min) °С -25
Ingress protection rating - IPX4
Ingress protection rating of the drive - IP44
Impeller material - Plastic
Trademark Vents
Model VKMK 250
Type of drive installed External MSD or VSD
Type of heat recovery system None
Nominal external pressure (Pa) 331
Maximum external leakage rates (%) 2.7
Static efficiency (%) 32.2
Declared typology NRVU UVU
Effective electric power input (kW) 0.182
Sound power level (dB(A)) 72
Datasheet
"VENTS VKMK" product description 10-2025
944 Kb
Manual
"VENTS VKMK, VKMKp" user's manual 06-2024 (V292EN-01)
801 Kb
Manual
"VENTS VKV, VKH, VKV EC, VKH EC, VKMK, VKMKp, VOK, VOK1" user's manual 01-2021 (V12EN-09)
2.05 Mb
Image
VKMK 250 - image 1
324 Kb
∅D ∅D1 H L L1
248 400 249 590 450
Name Photo Description
Vents RSA5E-3,5-T RSA5E-3,5-T Speed controllers are applied for air flow control of single phase fans by means of motor step speed control
Vents RSA5E-5,0-T RSA5E-5,0-T Speed controllers are applied for air flow control of single phase fans by means of motor step speed control
Vents RSA5E-7,5-T RSA5E-7,5-T Speed controllers are applied for air flow control of single phase fans by means of motor step speed control
Name Photo Description
Vents RKV 250-315 RKV 250-315 Mounting frame
Vents RKVI 250-315 RKVI 250-315 Mounting frame with thermal-insulating layer