| Unit of measurement | VKMz 200 Q | ||
| Connected air duct size | mm | 200 | |
| Phases | - | 1 | |
| Minimum supply voltage | V | 220 | |
| Maximum supply voltage | V | 240 | |
| Power supply frequency | Hz | 50 | 60 |
| Rated power | W | 130 | |
| Unit current | A | 0.56 | |
| Maximum airflow | m3/h | 900 | |
| Sound pressure level LpA at 3 m | dB(A) | 48 | |
| Weight | kg | 5.5 | |
| Transported air temperature (max) | °С | 50 | |
| Transported air temperature (min) | °С | -25 | |
| Ingress protection rating | - | IPX4 | |
| Ingress protection rating of the drive | - | IP44 | |
| Trademark | Vents |
| Model | VKMz 200 Q |
| Type of drive installed | Integrated VSD |
| Type of heat recovery system | None |
| Nominal flow rate (m3/s) | 0.137 |
| Nominal external pressure (Pa) | 308 |
| Maximum external leakage rates (%) | 2.7 |
| Static efficiency (%) | 33.6 |
| Declared typology | NRVU UVU |
| Effective electric power input (kW) | 0.128 |
| Sound power level (dB(A)) | 69 |