Vents VKP 125

Centrifugal fans in the steel casing for round ducts
  • Maximum airflow: 340 m3/h
  • Sound pressure level LpA at 3 m: 48 dB(A)
  • Motor type: AC
  • Impeller type: Centrifugal backward curved blades
  • Casing material: Coated steel
  • Installation in any position
Unit of measurement VKP 125
Connected air duct size mm 125
Minimum supply voltage V 220
Maximum supply voltage V 240
Power supply frequency Hz 50/60
Rated power W 58
Unit current A 0.26
Maximum airflow m3/h 340
Sound pressure level LpA at 3 m dB(A) 48
Weight kg 4.55
Transported air temperature (max) °С 50
Transported air temperature (min) °С -25
Ingress protection rating - IPX4
Ingress protection rating of the drive - IP44
Vents VKP 125 48 310 2016
Trademark Vents
Model VKP 125
Specific energy consumption (SEC) (kWh/(m2/a)) Cold Average Warm
-53.4 A+ -26.4 B -10.9 E
Type of ventilation unit Unidirectional
Type of drive installed Variable speed
Type of heat recovery system None
Maximum flow rate (m3/h) 310
Electric power input (W) 58
Reference flow rate (m3/s) 0.06
Reference pressure difference (Pa) 50
Specific power input (SPI) (W/(m3/h)) 0.147
Control typology Local demand control
Maximum external leakage rates (%) 2.7
Declared typology RVU UVU
Sound power level (dB(A)) 48
The annual electricity consumption (AEC) (kWh/a) Cold Average Warm
78 78 78
The annual heating saved (AHS) (kWh/a) Cold Average Warm
5536 2830 1280
Datasheet
"VENTS VKP (for round ducts)" product description 05-2023
991 Kb
Manual
"VENTS VKP, VKP mini" user's manual 05-2022 (V17EN-06)
1.74 Mb
BIM/CAD models
VKP round
2.2 Mb
Image
VKP 125 - image 1
304 Kb
Image
VKP 125 - image 2
520 Kb
Image
VKP 125 - image 3
828 Kb
∅D B H L L2
124 252 133 420 321