| Unit of measurement | VUT 3000 PE EC | |
| Connected air duct size | mm | 400 |
| Phases | - | 3 |
| Minimum supply voltage | V | 400 |
| Maximum supply voltage | V | 400 |
| Power supply frequency | Hz | 50/60 |
| Rated power | W | 1980 |
| Power of electrical reheater | W | 21000 |
| Unit current | A | 33.4 |
| Maximum airflow | m3/h | 4000 |
| Sound pressure level LpA at 3 m | dB(A) | 59 |
| Heat recovery efficiency, max | % | 75 |
| Heat exchanger type | - | Cross flow |
| Heat exchanger material | - | Aluminum |
| Weight | kg | 290 |
| Extract filter | - | G4 |
| Supply filter | - | G4 |
| Transported air temperature (max) | °С | 40 |
| Transported air temperature (min) | °С | -25 |
| Ambient air temperature min | °С | 1 |
| Ambient air temperature max | °С | 40 |
| Trademark | Vents |
| Model | VUT 3000 PE EC |
| Type of drive installed | Integrated VSD |
| Type of heat recovery system | Recuperative |
| Thermal efficiency of heat recovery (%) | 67 |
| Nominal flow rate (m3/s) | 0.609 |
| Nominal external pressure (Pa) | 739 |
| Maximum internal leakage rates (%) | 2.7 |
| Maximum external leakage rates (%) | 2.7 |
| Static efficiency (%) | 61.7 |
| Visual filter warning | See control panel catalogue data |
| Declared typology | NRVU BVU |
| Effective electric power input (kW) | 2.108 |
| Face velocity at design flow rate (m/s) | 0.994 |
| Energy performance of filters | B |
| Sound power level (dB(A)) | 79 |
| Name | Photo | Description |
|---|---|---|
| Vents SR 400/900 |
|
Silencers made of galvanized steel filled with non-combustible sound-absorbing material |
| Vents SR 400/1200 |
|
Silencers made of galvanized steel filled with non-combustible sound-absorbing material |
| Name | Photo | Description |
|---|---|---|
| Vents KRV 400 |
|
Air dampers for automatic air flow control in round ducts |
| Name | Photo | Description |
|---|---|---|
| Vents Belimo TF230 |
|
The actuators are designed for controlling air dampers with cross section up to 0.4 m² performing protection functions |
| Vents Belimo LF230 |
|
The Belimo LF series actuators are designed for controlling air dampers with cross section up to 0.8 m² performing protection functions |
| Name | Photo | Description |
|---|---|---|
| Vents SF 827x741x48 G4 |
|
Panel filter G4 |