Series Vents KNTK

Excess pressure valve
APPLICATION

KNTK valve is designed for installation on air ducts in a ventilation system to maintain and control the excess pressure in a defense structure. The valve provides one-way flow of air into adjacent premises.


DESIGN

The valve consists of a casing, which is a flange with a counterweighted disc that fits tightly against it. When excessive pressure is applied to the valve, the counterweights cause the disc to open the valve and allow air to flow freely. The valve has an extra flange used for welding it to the ventilation system's air ducts.
The valve is only installed in the vertical position. The allowed maximum deviation of the valve from the vertical is ±3°.

TECHNICAL DATA

The valve KNTK is designed for excessive pressure release in the range 20-150 Pa in compliance with the requirements stated in the DBN V.2.2.5-2023. The valve is made of powder-coated carbon steel in accordance with RAL 5007 Muar. The transported air temperature should be from -20 °C to +40 °C. The device can be operated in a temperate (Y) climate of the 2nd placement category (Y2) in compliance with the DSTU 15150 standard.

Datasheet
"KNTK" product description 03-2026
231 Kb
Datasheet
"Setting up ventilation systems in shelters" catalogue 2026
10.31 Mb
Manual
"KNTK" installation instruction 12-2024 (V299-3EN-01)
393 Kb
Image
KNTK - image 1
238 Kb