Series Vents VPVO

Axial fans with air flow up to 120 000 m³/h
  • Impeller type: Axial
PURPOSE

In general ventilation systems in industrial, administrative and residential buildings. As a part of a smoke extraction system for air pressurization to create a positive air pressure differential in stairway enclosures, airlock vestibules and lift shafts, to prevent spreading of smoke in premises, protect people using evacuation routes from fire hazards and enable conditions for fire-extinguishing measures.


DESIGN

The metal casing with rolled flanges helps achieve outstanding rigidity and minimum clearances between the casing and the blades. There is an inspection hatch in the casing for easy maintenance. All the casing components are powder coated for improved protection against the environmental effects. The weight of the fans may differ from the one stated in the catalogue and depends on the components used (motor, terminal box, etc.).


MOTOR

The fans are equipped with three-phase (400 V/50 Hz) single-speed 2-, 4- or 6-pole electric motors. Motor ingress protection level – IP55.

IMPELLER

Depending on the size and the required air capacity the fans are equipped with impellers with 6 or 8 blades angled from 20° to 50° with variation from 2.5 up to 5° to ensure precise matching of fans with the operating point. The specially designed impeller blades ensure high efficiency of the fan while keeping noise well under control. The impellers are dynamically balanced. Low weight and low moment of the impeller inertia help reduce the fan start-up time. The fan blades can be made of the following materials: PAG – fiberglass reinforced polyamide AL – aluminium. Please confirm the blade material while placing your order.


INSTALLATION

The fans can be mounted on any flat surface or directly into a ventilation duct. The units are suitable for both horizontal and vertical configurations. In-duct installation requires flanges to attach the fan to the ductwork. To attach the fan to the floor, a wall or the ceiling use the O-VO carriers (not included as standard, should be purchased separately). The units are suitable for installation on rooftops to provide direct supply of outdoor air to the stairway areas.

COMPLETE SOLUTIONS FOR AXIAL FANS


INSTALLATION EXAMPLE OF AXIAL FANS ON ROOFTOP


Filters: Connected air duct size: 630 mm
Lineup Vents VPVO Connected air duct size, mm Rated power, W Maximum airflow, m³/h Number of blades, pcs. Blade setting angle, degrees Impeller material
630 3000 15000 8 25 Aluminium
630 4000 19000 8 30 Aluminium
630 5500 24300 8 35 Aluminium
630 7500 27800 8 40 Aluminium
630 9200 28800 6 30 Aluminium
630 11000 31100 6 32.5 Aluminium
630 11000 33400 6 35 Aluminium
630 15000 35400 6 37.5 Aluminium
630 15000 37400 6 40 Aluminium
630 18500 40900 6 45 Aluminium
630 3000 15000 8 25 Fiberglass reinforced polyamide
630 4000 19000 8 30 Fiberglass reinforced polyamide
630 5500 24300 8 35 Fiberglass reinforced polyamide
630 7500 27800 8 40 Fiberglass reinforced polyamide
630 9200 28800 6 30 Fiberglass reinforced polyamide
630 11000 31100 6 32.5 Fiberglass reinforced polyamide
630 11000 33400 6 35 Fiberglass reinforced polyamide
630 15000 35400 6 37.5 Fiberglass reinforced polyamide
630 15000 37400 6 40 Fiberglass reinforced polyamide
630 18500 40900 6 45 Fiberglass reinforced polyamide
630 370 7500 8 25 Aluminium
630 550 9500 8 30 Aluminium
630 750 12200 8 35 Aluminium
630 1100 13900 8 40 Aluminium
630 1500 15600 6 32.5 Aluminium
630 1500 16500 8 45 Aluminium
630 1500 17700 6 37.5 Aluminium
630 2200 18700 6 40 Aluminium
630 2200 20400 6 45 Aluminium
630 370 7500 8 25 Fiberglass reinforced polyamide
630 550 9500 8 30 Fiberglass reinforced polyamide
630 750 12200 8 35 Fiberglass reinforced polyamide
630 1100 13900 8 40 Fiberglass reinforced polyamide
630 1500 15600 6 32.5 Fiberglass reinforced polyamide
630 1500 16500 8 45 Fiberglass reinforced polyamide
630 1500 17700 6 37.5 Fiberglass reinforced polyamide
630 2200 18700 6 40 Fiberglass reinforced polyamide
630 2200 20400 6 45 Fiberglass reinforced polyamide
Datasheet